Operation: Configuration Mode

3.1 Introduction
The Controller has two different modes of operation. The first, Run Mode, is used to display values for the process variable, setpoint value and to display or clear peak and valley values. The other mode, Menu Configuration Mode, is used to navigate through the menu options and configure the controller. Part 3 of this manual will explain the Menu Configuration Mode. For your controller to operate properly, the user must first "program" or configure the menu options in the Menu Configuration Mode.

Turning your Controller On for the First Time

The Controller becomes active as soon as it is connected to a power source. It has no On or Off button. The Controller will at first flash reset on the PV and software version number on the SV display, and then proceed to the Run Mode.

BUTTON
Function in Configuration Mode
MENU
To enter the Configuration Mode, the user must first press MENU. Use this button to advance/navigate to the next setting. The first menu to appear will be "ID Code", if enabled. The user can navigate through all the top level menus by pressing MENU. Selecting an ID of 0000 will allow you to bypass the ID menu using the MENU button.
/MAX
Press this button to scroll through "flashing" selections. When a numerical value is flashing, this button will increase the active digit from "0" to "9". After "9" the display starts at "0" again. The most significant digit may also show a "û" sign. In the run mode MAX causes the display to flash the PEAK - press again to return to the PV value.
/MIN
Press this button to go back to a previous Top Level Menu item. Press this button twice to reset the controller to the Run Mode. When a numerical value is flashing, this button will scroll through the digits from left to right digit allowing the user to select the desired digit to modify. In the run mode, MIN causes the display to flash the VALLEY - press again to return to the PV value.
ENTER
Press this button to access the submenus from a Top Level Menu item. Also, press this button to store a submenu selection or after entering a value ù the display will flash a "stored" message to confirm your selection. To reset flashing Peak or Valley press ENTER. In the run mode, press ENTER twice to enable standby mode with flashing "StbY".
NOTE:
Reset: Press MENU then MIN. NOTE: Push Button activations are designed to avoid momentary closures. Therefore, to activate a switch the button must be kept pressed for at least 300 m/sec. Except for Set Points and the Alarms, modifying any settings of the menu configuration will reset the controller prior to resuming run mode.

ID Number (if enabled)
*It is recommended that you put the controller in the standby mode for any configuration change other than setpoints & alarms*
SEE ID OPTION SUBMENU IN THE BREAK LOOP ALARM SECTION FOR ENABLE/DISABLE ID OPTION
Display Action Response
Press MENU
Press ENTER
ENTERING OR CHANGING YOUR (NON-DEFAULT) ID NUMBER.
1)
Press Menu, if necessary, until "Id Code" prompt appears.
2) Display advances to "id Cd", if non-default ID code. If default ID code, the menu will advance to Ck.Id with default value i.e. 0000.
Note: If the ID Code is the default value i.e. 0000, press MENU again and the menu will skip the ID code to Set Point menu.
Press MAX & MIN
Press ENTER
3) Press Max to increase digit 0-9. Press Min to activate next digit (flashing). Continue to use MAX and MIN to enter your 4-digit ID code.
4) If the correct ID code is entered, the menu will display CH.Id, otherwise an error message will be displayed and the controller will return to the run mode.
Press MENU or Press MAX & MIN 5) To leave your ID Code Unchanged, press MENU and advance to "set point" menu. To Change your ID code use the MAX and MIN buttons to enter a new ID code.
Press ENTER 6) Display flashes "strd" message and advances to the next menu "set point".
Note: To prevent unauthorized tampering with the setup parameters, the controller provides protection by requiring the user to enter the ID Code before allowing access to subsequent menus. If the ID code entered does not match the ID code stored, the controller responds with an error message and access to subsequent menus will be denied.
Tip: Use numbers that are easy for you to remember. If the ID code is forgotten or lost, call customer service with your serial number to reset the default to "0000".


Set Points (if ID Number Enabled)
Display Action Response
Press MENU
Press ENTER
SET POINT 1
1) Press MENU, if necessary, until "Set Pt" prompt appears.
2) Display advances to "SP1", set point 1.
Press MAX & MIN DISPLAY SHOWS PREVIOUS VALUE. 1ST DIGIT FLASHING.
4)
Press MAX to increase digit 0-9. Press MIN
5) Press MIN to activate next digit (flashing).
6) Continue to use MAX and MIN to enter your 4-digit Set Point 1 value.
Press ENTER 7) Display flashes "strd" message only if a change is made, otherwise press menu to advance to "SP2", set point 2.
Press MAX & MIN SET POINT 2: DISPLAY SHOWS PREVIOUS VALUE. 1ST DIGIT FLASHING.
9) Use MAX and MIN buttons to enter your 4-digit Set Point 2 value.
Press ENTER 13) Display flashes "strd" message and advances to "Swapping Set Pointsö submenu.
OUTPUT REDIRECTION: DISPLAY SHOWS "5 l.o.1" AND CURRENT SETTING, "5 l.o.1" OR "5 l.o.2"
When "5 l.o.1" is selected, Set-Point 1 (and OUT1 configuration) direct the control output at label "Output 1" and Set-Point 2 (and OUT2 configuration) direct the control output at label "Output 2." When "5 l.o.2" is selected , Set-Point 1 (and OUT1 configuration) direct the control output at label ôOutput 2ö and Set-Point 2 (and OUT2 configuration) direct the control at label "Output 1."
  Press MAX
Press MIN
14) Press MAX to select the output option.
15) Press ENTER to make the selection or MENU to advance to "Input Type".
NOTE: Always put unit in stand-by before redirecting the outputs, and always perform a reset afterward to ensure proper operation. With Analog Proportional output option, the following issues need to be consider when redirecting the output: 1) Current (4-20mA) output is disabled; 2) %Hi/Lo and SELF setting is moved to Out2 configuration menu; 3) Control Type and Cycle Time appear in Out1 and is associated with time proportional control at Output 2; 4) Control Type and Cycle Time setting in Out2 is disregard by Analog Proportional output.

Set Points (If ID Number Disabled-default)
Display Action Response
Press MENU
Press MAX
Press MIN
Press ENTER
With ID number disabled and in run mode, pressing MENU one time advances the controller to Set Point 1 setting directly.
SET POINT 1
1) Press MENU once from run mode. (1 time)
2) Display flashes the first digit of Set Point 1
3) Press MAX to set the digit, 0-9.
4) Press MIN to activate the next digit (flashing).
5) Repeat step 3 and 4 until all digits are set.
6) Controller stores new setting and returns to run mode.
Press MENU
(2 times)
1) Press MENU twice from run mode.
2) Display flashes the first digit of Set Point 2.
3) Follow step 3 to 6 of Set Point 1 to complete the setting.
Press MENU
(3 times)
Press MAX
Press ENTER
OUTPUT REDIRECTION
1) Press MENU 3 times from run mode.
2) Display flashes "5 l.o.1" in the SV window.
3) Press MAX to select the output option.
4) Press ENTER to make the selection or MENU to advance to "Input Type".

3.2 Menu Configuration: Modifying set points will not reset the controller.
Figure 3.1 Flowchart for ID and Set Point Menus
Figure 3.1 Flowchart for ID and Set Point Menus

Input Type (Thermocouple)

Display Action Response
Press MENU
Press ENTER
ENTER INPUT TYPE MENU:
1) Press MENU, if necessary, until "inpt type" prompt appears.
2) Display flashes "rtd", "t.c", or "proc" (RTD, Thermocouple, Process), if the displayed input type is Tc, press MENU to skip to step 5 (tc stops flashing).
Press MAX
Press ENTER
Press ENTER
THERMOCOUPLE SUBMENU:
3) Press MAX to scroll to "t.c" (flashing).
4) Display flashes "stored" message and "t.c" stops flashing.
5) Display flashes previous thermocouple type selection. ie. "J" (see below for types).
Press MAX
Press ENTER
6) Scroll through the available thermocouple types to the selection of your choice.
7) Display flashes "strd" message and advances to the next menu Reading Configuration
Note: Use the Input Type (Thermocouple) (RTD) or (Process) and verify your Dip Switch Setting (see section 2.4) and your Electrical Installation (see section 2.5). See the following pages for (RTD) and (Process) menus.
Thermocouple Types: (J, K, T, E, N, DIN J, R, S, B, C)
Display: J CA T E N DNJ R S B C

Input Type (RTD)
Display Action Response
Press MENU
Press ENTER
ENTER INPUT TYPE MENU:
1) Press MENU, if necessary, until "inpt type" prompt appears.
2) Display flashes "rtd", "t.c", or "proc" (RTD, Thermocouple, Process), if the displayed input type is rtd , press MENU to skip to step 5 (rtd stops flashing).
Press MAX
Press ENTER
Press ENTER
RTD SUBMENU:
3) Press MAX to scroll to "rtd" (flashing).
4) Display flashes "stored" message and "rtd" stops flashing
5) Display flashes previous RTD type selection ie. 392.2.
Press MAX
Press ENTER
6) Scroll through the available RTD types to the selection of your choice.
7) Display flashes "strd" message and advances to "rtd value".
RTD Types: 385, 392, Two, Three and Four-wire
Display: 392.2, 392.3, 392.4, 385.2, 385.3, 385.4
Note: Last digit indicates: 2, 3 or 4-wire input.

Input Type (RTD Value)
Display Action Response
Press ENTER RTD VALUE SUBMENU:
4) Press ENTER at "rtd valu" prompt to enter your RTD Value. Display flashes previous RTD value selection ie. 100 _ .
Press MAX 7) Scroll through the available RTD Values to the selection of your choice
Press ENTER 8) Display flashes "stored" message and advances to "Reading Configuration"
RTD Values: All RTDÆs may be: 100 ohm 500 ohm 1000 ohm
Display: 100 _ 500 _ 1000

Input Type (Process)
Display Action Response
Press MENU
Press ENTER
ENTER INPUT TYPE MENU:
1) Press MENU, if necessary, until "inpt type" prompt appears.
2) Display flashes "rtd", "t.c", or "proc" (RTD, Thermocouple, Process), if the displayed input type is Process, press MENU to skip to step 5 (rtd stops flashing).
Press MAX
Press ENTER
Press ENTER
PROCESS SUBMENU:
3) Press MAX to scroll to "Proc" (flashing).
4) Display flashes "stored" message and "Proc" stops flashing.
5) Display flashes previous Process type selection. ie. "0-10" (see below for types) InPt Proc
Press MAX
Press ENTER
6) Scroll through the available Process types to the selection of your choice.
7) Display flashes "stored" message and advances to " Reading Configuration".
NOTE: Use the Input Type (Thermocouple) (RTD) or (Process) and verify your Dip Switch Setting (see section 2.4) and your Electrical Installation (see section 2.5).


NOTE: For 4-20mA Input select 0-20mA and adjust the Input Scale & Offset accordingly. To adjust 4-20mA input. (see example under INPUT Scale & Offset)

Figure 3.2 Flowchart for Input Type
Figure 3.2 Flowchart for Input Type
Help Price List Specifications Print Manual Manuals Home
 Home Home  Table of Contents TOC  Back Back  Next Next